TABLE XIX. Conformance inspection.
Inspection
Requirement
Test method
Group A
Material (if specified)
Service A
Service C
Assembly
Appendix A
Resistance (cold)
Lubrication
Preload device (submarine motors
with special pre-load requirements
only)
Group B
Structureborne noise
Mechanical balance
Service A
Mechanical balance, continued.
Service C
End play
Sleeve bearing motors
Ball bearing motors
No-load input (induction motors)
Phase characteristic
(synchronous motors)
No-load test
Dielectric strength
Sealed insulation system
electrical
4.6 Test methods.
4.6.1 Materials. The Government may require material tests whenever it considers it necessary to ascertain that
the quality of a material used is at least equal to the material specified herein and covered by the referenced
specifications, or as shown on the manufacturer's drawing.
4.6.2 Assembly.
4.6.2.1 Service A motors. The inspections for Service A motors shall be as specified in Appendix A herein.
4.6.2.2 Service C motors. Each motor shall be visually examined to determine that construction and
workmanship conform to the requirements specified herein. The fit of parts shall be examined to determine the
interchangeability of parts which may require replacement during the service life of the motor.
4.6.3 Resistance (cold). With the motor not operating and at the ambient temperature, each terminal-to-
terminal winding resistance (cold) and the ambient temperature shall be measured.